Infrared Thermal Imaging for Electrical Systems in Manufacturing Plants and Large Facilities

Nov 9
4 min read

Most electrical failures we get called for did not happen all at once. A lug loosened. A breaker started running hot. A bus joint corroded. For months it was getting warmer, and nobody could see it. An infrared camera sees it.

If you run a manufacturing plant, a distribution center or any large facility in South Florida, an infrared scan of your electrical gear is one of the cheapest pieces of insurance you can buy. Here is what it finds, what the standards now say, and how to get a scan that is worth the money.

What a thermal scan actually finds

Electrical problems make heat before they make smoke. An infrared camera shows temperature differences across equipment while it runs under load. The usual findings:

  • Loose or poorly torqued connections at lugs, bus joints and breaker terminals

  • Overloaded conductors and breakers

  • Unbalanced phases, where one phase runs much hotter than the other two

  • Failing breakers, fuses and fuse clips

  • Hot spots in transformers, motor control centers and disconnects

The scan does not fix anything. It tells you where to look, how urgent it is, and what can wait for a planned shutdown. That last part is the value. Fixing a hot connection on a Saturday is a maintenance job. Fixing it after it fails on a Tuesday is a lost production day.

What NFPA 70B says now

For decades, NFPA 70B was a recommended practice. With the 2023 edition it became a standard, written in mandatory language that insurers, owners and authorities can enforce. The 2023 edition set infrared thermography of electrical equipment at least every 12 months as a baseline, and every 6 months for equipment in poor condition.

The current edition is 2026. One change worth knowing: it allows permanently installed, continuously monitoring temperature sensors to satisfy the thermography requirements. For gear that is hard or risky to open, that can be a better answer than an annual scan.

Insurers have noticed. Some now recommend annual infrared surveys at industrial sites as part of their risk programs. If your carrier has asked for a scan report, this is why.

Doing it safely

Many scans require opening covers on energized equipment. That is energized work, and NFPA 70E applies: a qualified person, a risk assessment, arc flash labeling you can trust, and the right PPE. Anybody who shows up and starts pulling panel covers without talking about that is the wrong crew.

Infrared windows installed in switchgear covers let a thermographer see inside without opening anything. On large switchgear and MCCs, we think they are worth installing, especially if you are scanning every year.

Getting a scan that is worth the money

Scan under real load. A hot connection at 20 percent load may look fine. Schedule the scan during normal production, not on a slow shift.

Get a real report. Each finding should have an image, a normal photo, the location, the load at the time, the temperature difference, and a priority. A stack of pretty pictures with no priorities is not a report.

Fix what you find, then rescan. The scan is only half the job. After repairs, a quick follow up image confirms the problem is gone.

Keep the history. Comparing this year to last year is where trends show up.

Why it matters more in South Florida

Our climate is rough on electrical gear. Humidity and salt air corrode connections. Rooftop and outdoor equipment bakes in the sun. Plants in Doral, Medley, Hialeah, Miramar, Pompano Beach and along the Riviera Beach industrial areas often run long hours with little downtime. And hurricane season brings power events that stress everything. A scan in the spring catches problems before the storms and the heat of summer find them first.

Beyond switchgear

The same camera helps on the mechanical side. Motor bearings, couplings and belt drives show heat when they start to fail. On chiller plants, a scan of the starter, the drive and the feeders is a smart add to annual maintenance. Because we do both electrical and HVAC, we can look at the whole plant in one visit. When a finding leads to planned construction work or a generator tie in, one team can carry both sides.

Schedule your scan

Pacman HVAC Electric Fire has served commercial and industrial facilities in Broward, Palm Beach and Miami Dade since 1999, under electrical license EC13006438. Puttshack in Dania Beach, Azura Surgery Center in Plantation and the Diplomat Hotel in Hollywood are among the projects on our list.

Frequently asked questions

How often does NFPA 70B want infrared scans?

The 2023 edition set infrared thermography of electrical equipment at least every 12 months as a baseline, and every 6 months for equipment in poor condition. The current 2026 edition also allows permanently installed, continuously monitoring temperature sensors to satisfy the thermography requirements.

Why scan under load instead of during a slow shift?

A hot connection at 20 percent load may look fine. Real production load is what shows loose lugs, overloaded breakers and unbalanced phases. Schedule the scan during normal operations so the report matches how the plant actually runs.

Why does South Florida need infrared scanning more?

Humidity and salt air corrode connections. Outdoor and rooftop gear bakes in the sun. Plants often run long hours with little downtime, and hurricane season brings power events that stress everything. A spring scan catches problems before summer heat and storms find them first.